ANALISIS KEANDALAN SISTEM DISTRIBUSI 20 KV PADA PENYULANG JOLOTUNDO DENGAN METODE FAILURE MODE EFFECT ANALYSIS (FMEA)-FUZZY-PSO UNTUK PENEMPATAN RECLOSER

Fadilah, Alif (2023) ANALISIS KEANDALAN SISTEM DISTRIBUSI 20 KV PADA PENYULANG JOLOTUNDO DENGAN METODE FAILURE MODE EFFECT ANALYSIS (FMEA)-FUZZY-PSO UNTUK PENEMPATAN RECLOSER. Undergraduate thesis, Universitas Muhammadiyah Malang.

[thumbnail of PENDAHULUAN.pdf]
Preview
Text
PENDAHULUAN.pdf

Download (738kB) | Preview
[thumbnail of BAB I.pdf]
Preview
Text
BAB I.pdf

Download (74kB) | Preview
[thumbnail of BAB II.pdf]
Preview
Text
BAB II.pdf

Download (282kB) | Preview
[thumbnail of BAB III.pdf]
Preview
Text
BAB III.pdf

Download (783kB) | Preview
[thumbnail of BAB IV.pdf] Text
BAB IV.pdf
Restricted to Registered users only

Download (235kB) | Request a copy
[thumbnail of BAB V.pdf] Text
BAB V.pdf
Restricted to Registered users only

Download (58kB) | Request a copy
[thumbnail of LAMPIRAN.pdf] Text
LAMPIRAN.pdf
Restricted to Registered users only

Download (94kB) | Request a copy
[thumbnail of POSTER.pdf] Text
POSTER.pdf
Restricted to Registered users only

Download (394kB) | Request a copy

Abstract

The reliability of the distribution channel can be seen from the ability of the electric power distribution system to consistently deliver energy to loads or customers with high reliability. Higher values of reliability indices reflect lower levels of reliability and a decrease in service quality. One strategy to enhance the reliability of the distribution network is the optimization of the use of devices such as reclosers. This research stems from the urgent need to improve the reliability of the Jolotundo feeder system. Initial analysis using the Failure Mode Effect Analysis (FMEA) method revealed that the reliability index of the feeder did not meet PLN standards. By implementing Fuzzy Logic, three sections out of a total of eight were selected as a priority for recloser placement. Particle Swarm Optimization (PSO) was then utilized to find the optimal location for the recloser and minimize the reliability index value. Test results showed a significant decrease in SAIFI and SAIDI values after the installation of the recloser, with the lowest decrease occurring on bus 67, namely SAIFI 1.721209, and SAIDI 5.243459. As for the CAIDI value, it remained stable despite fluctuations, which were not too significant. Additionally, the ASAI, while consistently improving in performance, did not show substantial changes. Bus 67 was consistently chosen as the optimal recloser placement location among other buses in each section selected for optimization.

Item Type: Thesis (Undergraduate)
Student ID: 201810130311105
Keywords: SAIDI, SAIFI, Distribution Reliability, Recloser, Failure Mode Effect Analysis, Fuzzy Logic, PSO
Subjects: A General Works > AS Academies and learned societies (General)
T Technology > T Technology (General)
T Technology > TK Electrical engineering. Electronics Nuclear engineering
T Technology > TX Home economics
Divisions: Faculty of Engineering > Department of Electrical Engineering (20201)
Depositing User: 201810130311105 alfatujuh10gmailcom