PERENCANAAN STRUKTUR BAWAH GEDUNG POLIKLINIK RUMAH SAKIT SAKINAH MOJOKERTO MENGGUNAKAN PONDASI TIANG BOR (BORED PILE)

Riaviana, Elvira Nova (2023) PERENCANAAN STRUKTUR BAWAH GEDUNG POLIKLINIK RUMAH SAKIT SAKINAH MOJOKERTO MENGGUNAKAN PONDASI TIANG BOR (BORED PILE). Undergraduate thesis, Universitas Muhammadiyah Malang.

[thumbnail of PENDAHULUAN.pdf]
Preview
Text
PENDAHULUAN.pdf

Download (1MB) | Preview
[thumbnail of BAB I.pdf]
Preview
Text
BAB I.pdf

Download (246kB) | Preview
[thumbnail of BAB II.pdf]
Preview
Text
BAB II.pdf

Download (1MB) | Preview
[thumbnail of BAB III.pdf] Text
BAB III.pdf
Restricted to Registered users only

Download (654kB) | Request a copy
[thumbnail of BAB IV.pdf] Text
BAB IV.pdf
Restricted to Registered users only

Download (1MB) | Request a copy
[thumbnail of BAB V.pdf] Text
BAB V.pdf
Restricted to Registered users only

Download (145kB) | Request a copy
[thumbnail of LAMPIRAN.pdf] Text
LAMPIRAN.pdf
Restricted to Registered users only

Download (1MB) | Request a copy

Abstract

The use of bored pile foundations in high-rise buildings that aim to withstand the forces acting on the upper structure of the building. Based on analysis using the V8i STAAD.Pro application the largest axial load occurred at the E-10 grid column point, which was 469,602 tons. It is planned that the foundation of the drilled pile diameter is 0,6 m with a carrying capacity per pile 190,189 tons and a group pile carrying capacity 478,433 tons for a depth 15 m. Pile cap is planened in 6 types, where pile cap type 3 has dimension of 3 m x 1,5 m x 1 m, types 2 has dimension of 4,5 m x 1,5 m x 1 m and types 1 has dimension 2 m x 2 m x 0,7 m. Pile cap types 6 is the largest types because it bears the largest axial load, with an arrangement of reinforcement D22 -100 mm for repeating pile cap directions x and y, while for reinforcement for D19 – 150 mm and for repeating drill piles with dimensions of 60 cm using reinforcement 8D-22 mm, with spiral reinforcement D10 – 50. The and for repeating drill piles with dimension largest decrease occurred in types 6 pile cap of 3,83 cm with a period of 43 years. Reductions in tall buildings are required to meet the equation S <15+b/600 and obtain 3,83 <16,67 cm, thus fulfilling the equation based on (SNI 8460-2017:178) on Geotechnis.

Item Type: Thesis (Undergraduate)
Student ID: 201910340311201
Keywords: Bored Pile, Bearing capacity, Pile Cap, Reinforcement, Settlement
Subjects: T Technology > TA Engineering (General). Civil engineering (General)
Divisions: Faculty of Engineering > Department of Civil Engineering (22201)
Depositing User: 201910340311201 elviranova
Date Deposited: 23 Nov 2023 07:33
Last Modified: 23 Nov 2023 07:33
URI: https://eprints.umm.ac.id/id/eprint/1307

Actions (login required)

View Item
View Item